ElectroCalc

COMPONENTS / PARAMETER SIZING

Contactor Selection

Check motor operating current, utilization category and control coil.

Input Parameters

Edit the example values. Results update as you type.

Enter circuit voltage for single phase and line voltage for three phase.

Results

Reference Rated Operational Current
32 / 38A
Motor Operating Current
30A
Utilization Category
AC-3
Control Coil
24 V DC

Formula

Iₑ (at the utilization category and Uₑ) ≥ Iᴮ

Substitution

Iₑ(AC-3,380 V)≥ 30 A

Calculation Steps

  1. Uses the known or imported motor operating current.
  2. Screen for utilization category AC-3; cross-check the manufacturer's power rating for a 15 kW motor at this voltage.
  3. Select coil 24 V DC; verify NO / NC auxiliary contacts for self-holding, interlocking and feedback.

Result Explanation

Reference ratings are screened by AC-3 current. Verify manufacturer ratings at the actual voltage, load and operating frequency.

Product Candidates

Parameter-matched candidates
Schneider · TeSys D / DecaOfficial source

LC1D32BD

LC1D32BD

3P · AC-3 32 A · 15 kW @380–400 V · 24 V DC coil

  • Rated current covers the required current
  • Motor power rating has been checked for the voltage covered by this library

Rated margin above screening requirement: 6.7%

Schneider Electric · LC1D32BD data sheet ↗

Verified 2026-11-05

Schneider · TeSys D / DecaOfficial source

LC1D38BD

LC1D38BD

3P · AC-3 38 A · 18.5 kW @380–400 V · 24 V DC coil

  • Rated current covers the required current
  • Motor power rating has been checked for the voltage covered by this library

Rated margin above screening requirement: 26.7%

Schneider Electric · LC1D38BD data sheet ↗

Verified 2026-11-05

Formulas and FAQ

Iₑ (at the utilization category and Uₑ) ≥ Iᴮ
How do I select for frequent jogging or plugging?

Check manufacturer AC-4 current ratings, electrical life and operating frequency.