Schneider · Phaseo / Modicon ABL8Official source
ABL8RPS24030
ABL8RPS24030
24 V DC · 3 A · 72 W
Rated margin above screening requirement: 224.3%
Schneider Electric · Official Modicon ABL8 Selection Guide ↗Verified 2026-11-05
COMPONENTS / PARAMETER SIZING
Total DC loads such as PLCs, instruments and relays to estimate supply capacity.
Edit the example values. Results update as you type.
Ptotal = Σ(n × Punit) · Itotal = Ptotal / 24 · Ptarget = Ptotal × (1 + reserve ratio)Ptarget = 17.76 × (1 + 25%) = 22.2 WA default 25% reserve is used for preliminary sizing. Verify simultaneous solenoid pickup, capacitive-load startup and high-temperature derating separately.
| Load | Quantity | Per-Unit Input | Subtotal |
|---|---|---|---|
| PLC | 1 | 12 W | 12 W |
| Sensor | 4 | 0.06 A | 5.76 W |
ABL8RPS24030
24 V DC · 3 A · 72 W
Rated margin above screening requirement: 224.3%
Schneider Electric · Official Modicon ABL8 Selection Guide ↗Verified 2026-11-05
ABL8RPS24050
24 V DC · 5 A · 120 W
Rated margin above screening requirement: 440.5%
Schneider Electric · Official Modicon ABL8 Selection Guide ↗Verified 2026-11-05
ABL8RPS24100
24 V DC · 10 A · 240 W
Rated margin above screening requirement: 981.1%
Schneider Electric · Official Modicon ABL8 Selection Guide ↗Verified 2026-11-05
P_total = Σ(n × P_unit) · P_target = P_total × (1 + reserve)Check coincident pull-in or startup peaks, supply peak capacity and temperature derating.