Circuit Breaker Selection

Screen reference ratings by load type, starting method and operating current.

Input Parameters

Edit the example values. Results update as you type.

Enter circuit voltage for single phase and line voltage for three phase.

Enter ampacity after derating for actual conditions.

Results

Reference Rated Current
40 / 50A
Operating Current Iᴮ
30A
Screening Current
36A
Suggested Pole Count
3P (verify 4P when neutral disconnection is required)

Cable ampacity has not been entered. Verify Iₙ ≤ Iᴢ and conventional operating-current conditions for the listed ratings.

Formula

Iscreen = Iᴮ × k · Iᴮ ≤ Iₙ ≤ Iᴢ

Substitution

Iscreen = 30 × 1.2 = 36 A

Calculation Steps

  1. Uses the entered load operating current.
  2. Apply a preliminary margin for the load type, then screen common ratings against current and known ampacity limits.
  3. Verify voltage rating, prospective short-circuit current, breaking capacity, trip curve and protection coordination.

Result Explanation

Check closing inrush, time-current curves and upstream/downstream selectivity.

Product Candidates

Parameter-matched candidates
Schneider · Acti9 iC60NOfficial source

A9F74340

A9F74340

3P · Curve C · 40 A · Icn 6 kA (IEC 60898-1); verify breaking capacity at the actual voltage

  • Rated current covers the required current

Rated margin above screening requirement: 0%

Lifecycle status varies by region. Sales have ended in some regions. Verify local product status before purchasing.

Schneider Electric · A9F74340 Singapore product page ↗

Verified 2026-11-05

Formulas and FAQ

Iᴮ ≤ Iₙ ≤ Iᴢ · I_screen = Iᴮ × k
Can load current determine breaking capacity?

Check prospective fault current at the installation point and verify coordination and trip conditions against manufacturer requirements.