ElectroCalc

COMPONENTS / PARAMETER SIZING

Cable Selection

Screen conductor cross-sections using current, length, installation method and ambient temperature.

Input Parameters

Edit the example values. Results update as you type.

Enter circuit voltage for single phase and line voltage for three phase.

Enter a decimal greater than 0 and no greater than 1.

The aluminum-conductor table starts at 16 mm².

Reference table range: 10–60 °C.

Allocate a voltage-drop budget to this section.

The ampacity reference table uses PVC 70 °C conditions.

Used for steady-state voltage drop; verify against manufacturer data.

Results

Reference Conductor Cross-Section
6mm²
Operating Current
30A
Corrected Ampacity
34A
Voltage Drop
7.702V
Voltage Drop (%)
2.027%

Formula

Iᴢ = Itable × ktemperature · Iᴢ ≥ max(Iᴮ, Iprotection) · ΔU% = ΔU / U × 100%

Substitution

Iᴢ = 34 × 1 = 34 A ≥ 30 A;ΔU = 2.027% ≤ 3%

Calculation Steps

  1. Determine operating and known protection currents, then look up reference ampacity by material, phases and installation method.
  2. Ambient-temperature correction factor: 1. Voltage drop is estimated at conductor temperature 70 °C and reactance 0.08 Ω/km.
  3. Check corrected ampacity and steady-state voltage drop at each size; select the smallest cross-section meeting both requirements.

Result Explanation

Reference table for a single PVC cable circuit in air. Verify grouping, harmonics, starting, short-circuit thermal withstand and terminal requirements separately.

Conductor Cross-SectionCorrected AmpacityVoltage DropAmpacity / Voltage Drop
1.5 mm²14.5 A8.021%Insufficient / Over Limit
2.5 mm²19.5 A4.824%Insufficient / Over Limit
4 mm²26 A3.026%Insufficient / Over Limit
6 mm²34 A2.027%Pass / Pass
10 mm²46 A1.228%Pass / Pass
16 mm²61 A0.778%Pass / Pass
25 mm²80 A0.5083%Pass / Pass

Product Candidates

Parameter-matched candidates

Parameter sizing is available. No model in the current library meets these conditions.

Formulas and FAQ

Iᴢ = I_table × k_temperature · ΔU% = ΔU / U × 100%
Which installation conditions are covered?

Reference data covers single-circuit PVC cables in air. Grouping, buried cables, harmonics and special installations need separate checks.