Cable Voltage Drop

Estimate steady-state single-phase or three-phase cable voltage drop and percentage.

Input Parameters

Edit the example values. Results update as you type.

Enter circuit voltage for single phase and line voltage for three phase.

Enter a decimal greater than 0 and no greater than 1.

Default estimate; replace with manufacturer data when available.

Enter reliable active power at the load end to calculate transmission efficiency.

Used to correct candidate cable ampacity; range: 10–60 °C.

Results

Steady-State Voltage Drop
7.702V
Relative Voltage Drop
2.027%
Conductor Resistance
3.438Ω/km
Conductor Loss
464.122W
Transmission Efficiency
Enter load-end active power
Reference Cross-Section
6mm²

Formula

ΔU ≈ k × I × L × (R′ × cosφ + X′ × sinφ) · ΔU% = ΔU / U × 100% · Ploss = 3 × I² × R′ × L

Substitution

ΔU ≈ √3 × 30 × 50 × (0.003437943 × 0.85 + 0.00008 × √(1 − 0.85²)) = 7.702 V

Calculation Steps

  1. Convert cross-section to 0.000006 m²; calculate R′ using the resistivity of Copper at 70 °C.
  2. Use voltage-drop factor √3; divide the drop by 380 V to obtain 2.027%.
  3. Sum losses across 3 current-carrying conductors: Ploss = 3 × 30² × 0.003437943 × 50 = 464.122 W.
  4. Candidates use the same conductor temperature and reactance to estimate drop and loss; check against 30 °C ambient, installation method B2 and a 3% drop budget.

Result Explanation

Steady-state approximation for lagging power factor. Efficiency includes conductor loss only. Candidate ampacities use a single-circuit PVC 70 °C reference table. The five cross-sections nearest the recommendation are shown; sizes without ampacity data are excluded.

Conductor Cross-SectionDrop VDrop %Loss WAmpacity CheckVoltage-Drop CheckOverall Status
2.5 mm²18.3314.8241,113.89419.5 A · InsufficientOver LimitReview required
4 mm²11.4983.026696.18426 A · InsufficientOver LimitReview required
6 mm²7.7022.027464.12234 A · PassPassRecommended Reference
10 mm²4.6651.228278.47346 A · PassPassMeets Requirements
16 mm²2.9570.778174.04661 A · PassPassMeets Requirements

Formulas and FAQ

ΔU ≈ k × I × L × (R′ × cosφ + X′ × sinφ)
Why is the length one-way?

The single-phase factor 2 includes the outgoing and return conductors. Balanced three-phase circuits use √3.