ElectroCalc

ELECTRICAL / CALCULATOR

Power Factor Correction

Estimate compensation for an inductive load and single-phase, star or delta capacitor values.

Input Parameters

Edit the example values. Results update as you type.

Enter capacitor terminal voltage for single phase and line voltage for three phase.

Results

Required Capacitive Compensation Qc
42.132kvar
Initial Phase Angle φ₁
36.87°
Target Phase Angle φ₂
18.195°
Initial Apparent Power
125kVA
Corrected Apparent Power
105.263kVA
Initial Reactive Power
75kvar
Corrected Reactive Power
32.868kvar
Capacitance per Phase C
279.394μF
Capacitor Connection / Count
Three-Phase Delta / 3 capacitors

Formula

φ₁ = acos(PF₁) · φ₂ = acos(PF₂) · Qc = P(tanφ₁ − tanφ₂) · Cper phase = Qc / (3 × 2πf × U²)

Substitution

Qc = 100 × (tan(acos(0.8)) − tan(acos(0.95))) = 42.132 kvar;C = 42,131.589 / (3 × 2π × 50 × 400²) = 279.394 μF

Calculation Steps

  1. Assuming constant active power, calculate initial and corrected phase angles, apparent power and inductive reactive power.
  2. Total compensation Qc = Q₁ − Q₂ = 42.132 kvar; convert to 42,131.589 var for capacitance.
  3. Calculate per phase capacitance for Three-Phase Delta; use line voltage for three-phase systems.

Result Explanation

For shunt-capacitor correction of inductive loads in sinusoidal steady state. Qc is total compensating reactive power. Capacitance is a preliminary estimate; verify equipment nameplates and site conditions.

Formulas and FAQ

Qc = P × (tanφ₁ − tanφ₂)
Is the three-phase capacitance per phase or total?

The value is per phase for three capacitors. Enter line voltage. Star capacitance is Qc/(ωUᴸ²) and delta is Qc/(3ωUᴸ²). Qc is total three-phase compensation.